Specifications
Primary Input Power: 120VAC, 60Hz, 3.6A standard;
240VAC, 50Hz, 1.5A on units with E suffix.
Secondary Power: 24 volt operation: two 7-24 AH batteries.
Battery Charging Capacity: Up to 26 AH batteries.
HPFF8 Cabinet: Holds up to two 18AH batteries.
HPFF8CM: Holds up to two 12AH batteries.
Total Output Current: 8.0A max.
Standby Current: 0.075 A.
Auxiliary Power Output: 2.0A under all conditions.
NAC Output Ratings: 24VDC fully regulated, 3.0A max per circuit (8.0A total).
End-of-Line Resistor Range: 1.9K to 25k ohm, ½ watt.
Common Trouble: 2.0A at 30VDC.
Relay Fail Relay: 2.0A at 30VDC.
Input Control Circuits: compatible with 12 and 24 VDC control panel NACs.
Input Control Current (alarm): 5.68 mA @ 12 VDC, 12.28 mA @ 24 VDC.
Temperature Rating: 32°F to 120°F (0°C to 49°C).
Relative Humidity: 10% to 93% non-condensing.
Cabinet Dimensions:
• HPFF8 Cabinet: 16.65" W x 19.0" H x 5.2" D (42.29 W x
48.26 H 13.23 D cm)

 


 